Work Practices for Laboratory Fume Hoods
Laboratory fume hoods are designed to provide protection for the user from
chemical and radiological contaminants which are used inside the hood. Use of
Toxic and/or volatile chemicals should always occur in the fume hood, NOT on an
open bench. It should be noted that though fume hoods are designed to protect
the user from the hazardous substances being used, fume hoods DO NOT absolutely
eliminate exposure even under ideal conditions. Careless work practices can
cause considerable exposure to a user who may believe s/he is protected. To
optimize the performance of the fume hood the following work practices must be
adhered to:
- Ensure that your fume hood has a current inspection sticker (dated within
the last year). The Division of Environmental Health and Safety (DEHS)
measures fume hood velocities during the summer months. The face velocity
(which is written on the sticker) should be between 80 and 120 lineal feet per
minute (fpm). Contact your departmental business representative if the face
velocity is not within these limits. They can arrange to have the fume hood
exhaust system repaired.
- Verify that the fume hood is drawing air by checking the fume hood
monitor, if there is a monitor, or by taping a "Kimwipe" to the sash and
checking its position. If the draw does not seem sufficient check the fume
hood inspection sticker. If the sticker indicates that the hood maintained
adequate flow when it was inspected, have the hood checked again by DEHS
(4-8346) or Operations and Maintenance (O&M, 3-0340). DEHS does not charge to
check face velocities but will not repair the hood. O&M charges to check and
repair the hood.
- If there is a fume hood monitor which alarms during normal use, mute the
alarm, (if possible) and contact DEHS to check the air flow or have your
department business office arrange for repair to the monitor or hood exhaust
system.
- Utilize the hood with the sash positioned at the arrow on the fume hood
inspection sticker (usually 18 inches in height). This will ensure adequate
face velocity and allow the sash to act as a protective shield. If this height
is not appropriate for you, contact DEHS to measure the face velocity when the
sash is in your preferred position.
- Do not put your head in the hood when contaminants are being generated.
(This sounds incredibly basic but is a common occurrence.)
- Perform all work and keep all apparatus at least six (6) inches into the
hood.
- The fume hood is NOT a storage cabinet! DO NOT store chemicals or
apparatus in the hood. These stored materials can obstruct the air flow or
exacerbate an incident or emergency in the hood.
- Do not block the slots in the hood baffle with containers or apparatus. If
small amounts of chemicals or reagents must be stored in the hood, have
shelves installed on the sidewall of the hood. If large equipment is used in
the hood, place the equipment on blocks, legs or a low shelf, so that air can
flow underneath the equipment to the bottom slot of the baffle.
- Electrical receptacles (including power strips) must be located outside of
the fume hood. Ensure that there are no sources of ignition or spark,
including variable transformers (Variacs), when flammable liquids or gases are
present.
- Do NOT use perchloric acid heated above ambient temperature in a fume hood
unless it is specifically designed for this use, e.g., it is equipped with a
water wash down system.
- Keep fume hood sashes closed down to about a six (6) inch opening when the
hood is not in use. This will conserve energy in variable air volume systems
and act as a shield in the event of an unexpected release.
For additional information about fume hood use and general laboratory safety
refer to the Chemical Hygiene Plan.